AEG Electrolux PERFECT DB 50 Manual do Utilizador Página 10

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 24
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 9
10
Protect B
Protect B: Uninterruptible security with sine wave output for server and network components.
Ease of use
Flexible use,
intelligent functions
Modern VI (line-interactive)
protection technology with sine wave
output voltage
Compact construction and variable
use due to combination design
tower/rack
Robust design: overload capability
and short circuit protection
Overvoltage protection
(RJ11/RJ45) for phone,
fax, modem and network
User-friendly battery design
in hot-swappable configuration
(from 1500 VA)
Operator-friendly display
for optimal readability /
configuration
Intelligent monitoring system with
USB and RS232 interfaces
Communication slot for expansion
boards, e. g. SNMP (from 1500 VA)
24 month warranty
with advanced replacement service
Protect B. operator panel
Battery capacity
UPS capacity utilisation
Mains operation
Battery operation
Operating mode
UPS On/Off button
LEDs for fault
diagnosis
Rated output voltage
Configuration
Confirmation button
UPS test switch
Protect B.1500 & B.2000 • rear view
UPS input
UPS feed module
EPO
USB
RS232
Slot for AC output distribution
Communication slot
for expansion boards
Connection for external battery module
Overvoltage protection for
data interface, phone,
fax, modem or network
RS232
EPO
Communication slot for expansion boards
UPS feeds
Overvoltage protection for data
interface, phone, fax, modem or
network
UPS input
Height = 2 U
USB
Connection
for external
battery module
Miniature circuit
breakers for output
sockets
Protect B. Rack autonomy time (full/half load) [min.]
750 VA 1000 VA 1500 VA 2000 VA 3000 VA
Standard autonomy time 5/15 5 /15 5 /15 5/14 5/14
1 additional 19" battery insert - - 30/80 27/65 24/55
2 additional 19" battery insert - - 65/150 50/110 45/90
3 additional 19" battery insert - - - - 55/140
4 additional 19" battery insert - - - - 75/180
Protect B. Tower autonomy time (full/half load) [min.]
750 VA 1000 VA 1500 VA 2000 VA 3000 VA
Standard autonomy time 5 /15 5 /15 no integrated battery 5/14
1 additional battery module - - 5/15 5/14 24/55
2 additional battery modules - - 15/45 15/35 45/90
3 additional battery modules - - 30/80 27/65 55/140
4 additional battery modules - - 50/110 40/85 75/180
5 additional battery modules - - 65/150 50/110 -